PGG-EG Governor/Actuator
For Electrical Generation Application
PGG-EG governor/actuators have motor speed setting of the ballhead
backup governor. The units are normally used on generator applications.
Externally adjustable droop on the backup governor and load limit
are standard on the PGG-EG.
Setting the speed of the mechanical governor slightly higher than
the maximum speed under electronic control causes the mechanical
portion of the PGG-EG to always seek a fuel setting higher than
the electronic control. Electrical control thus controls the fuel
position because of the least-fuelselection feature.
Should the electronic signal to the reverse acting PGG-EG fail,
due to some problem in the system, the electric actuator will call
for an increased fuel position, above the setting of the mechanical
governor. At this point the mechanical speed setting is lower, and
the ballhead controls the engine-fuel setting.
PGG governor/actuators are available with any of the PG output
systems. Output ranges from 16 N m (12 lb-ft) maximum work capacity
to 678 N m (500 lb-ft), depending on the governor operating pressure
and the output options selected. Most outputs provide 30° of rotary
travel (25 mm [1 inch] of linear travel is also available).
PGG-EG governors may be equipped with lube oil pressure and water
pressure alarm and shutdown.
Contact GCS for product specifications
and technical manuals
|