Liquid Shutoff Valve
The Liquid Shutoff Valve is a three-way
valve designed to rapidly shut off all liquid
fuel flow and prevent leakage to the
turbine. In the de-energized state, the
valve diverts inlet flow to bypass ports,
preventing pressure damage to positive
displacement fluid systems.
Normal installation of the 21.5 pound (9.8
kg) valve is in the fuel line between the
fuel regulating valve and the turbine.
The valve diverts flow from the discharge to bypass ports anytime
the operating electrical signal is lost. The valve is available
in four voltage configurations. The valve is designed for a normal
operating supply pressure of up to 1200 psig (8274 kPa) and has
a rated flow of 30 000 lb/h (13 600 kg/h) (based on US MIL-C-7024
calibrating fluid at 70 °F/ 21 °C.)
|
|