![]() |
|
|||||||||
|
GCS CONTINUOUS EMISSIONS CATALYST MONITORING SYSTEM GCS developed a turnkey Continuous Parameter Emissions Monitor (CPMS) in a pre-wired NEMA enclosure utilizing the Dynalco Catalyst Monitor, which is configured for monitoring, maintaining and data logging specific parameters as required by RICE NESHAP*.
Specifications:
* MEETING RICE-NESHAP REQUIREMENTS(Reciprocating Internal Combustion Engines National Environmental Standards for Hazardous Air Particles) EPA requires that each Catalyst have a CPMS (Continuous Parameter Monitoring System) that monitors the inlet temperature and differential pressure of the catalyst. Catalyst inlet temperature must be maintained between 750°F and 1250°F. Compliance is based on 4-hour rolling averages(measured every 15 minutes). Pressure drop across the catalyst must not change by more than 2 inches water column at 100% load ±10% from the pressure drop measured during the initial performance test (measured once per month).
Contact GCS for product specifications and technical manuals |
|||||||||